RONG Fei,LI Wenjun,RAO Hong,ZHOU Baorong,HUANG Shoudao.Optimization Method for Switching Frequency of Converter Valve in MMC Flexible DC Transmission System[J].JOURNAL OF POWER SUPPLY,2018,16(6):84-91
Optimization Method for Switching Frequency of Converter Valve in MMC Flexible DC Transmission System
Received:March 10, 2017  Revised:March 10, 2018
View Full Text  View/Add Comment  Download reader
DOI:10.13234/j.issn.2095-2805.2018.6.84
Keywords:modular multi-level converter(MMC) valve  calculation of loss  harmonic analysis  linear weighted weight  genetic algorithm
Fund Project:National key R &D plan
              
AuthorInstitutionEmail
RONG Fei College of Electrical and Information Engineering, Hunan University, Changsha , China rf_hunu@126.com
LI Wenjun College of Electrical and Information Engineering, Hunan University, Changsha , China
RAO Hong State Key Laboratory of High Voltage Direct Current Transmission, Electric Power Research Institute, China Southern Power Grid, Guangzhou , China
ZHOU Baorong State Key Laboratory of High Voltage Direct Current Transmission, Electric Power Research Institute, China Southern Power Grid, Guangzhou , China
HUANG Shoudao College of Electrical and Information Engineering, Hunan University, Changsha , China
Hits: 560
Download times: 336
Abstract:
      A modular multi-level converter(MMC) valve is usually used in a flexible DC transmission system, and the magnitude of the switching frequency is closely related to system loss and AC-side harmonic content. In this paper, the mathematic expressions of MMC switching frequency vs. system loss and switching frequency vs. AC-side harmonic content of the flexible DC transmission system are deduced, respectively; in addition, the influences of MMC switching frequency on system loss and AC-side harmonics are analyzed. On this basis, in consideration of the loss and power quality of the flexible DC transmission system, genetic algorithm is used to optimize the switching frequency. According to engineering experiences, different weights are given to the corresponding optimization objectives. Following the Chinese national standard, the constraint conditions of harmonics and loss are set. Simulation results show that the flexible DC transmission system has better performance when using the optimized switching frequency to control the MMC converter.